oc· Delta MS300

Delta MS300 oc overcurrent fault: what to check

The MS300 does not just say "oc": it separates overcurrent by when it happens. That trailing letter is the diagnosis, because it narrows the problem to acceleration, deceleration or normal running.

What causes it

  • During acceleration: a ramp too fast for the inertia or for the torque the machine needs to start.
  • During deceleration: a stopping ramp that is too short.
  • At steady speed: a sudden load change, something jammed or material built up in the machine.
  • A short circuit between output phases or to ground, often from damaged cable or moisture in the motor terminal box.
  • A motor undersized for the job, or motor parameters loaded incorrectly in the drive.

How to diagnose it

  1. 1Write down the exact variant shown on the display. Accelerating, decelerating and steady running are solved in different ways.
  2. 2Remove power, apply lockout/tagout and wait for the bus to discharge. Then disconnect the motor and measure insulation between phases and to ground: that rules out a short circuit, the only urgent item on the list.
  3. 3Turn the shaft by hand if the machine allows it. A seized bearing or jammed material is found in thirty seconds and explains many steady-state overcurrents.
  4. 4If insulation is fine and the mechanics turn freely, lengthen the ramp that matches the variant and test again.
  5. 5Check the motor nameplate data loaded in the drive. A wrongly parameterized motor forces currents the drive reads as a fault.

Work on an energized panel: apply lockout/tagout and follow your plant procedure. This sheet guides the diagnosis, it does not replace it, and the manufacturer manual overrides anything written here.

When the warning comes too late

Current rises before it reaches the threshold. A failing bearing or a conveyor that starts carrying more load shows up in the trend weeks before the drive protects itself.

Start without hardware

Safe industrial AI, starting free from the app.

The app gathers what your team knows: each trade with its helpers, and @igromi answers citing the source. AI reads, proposes and cites; a person decides. When you add systems and equipment, the Edge reads PLCs in read-only mode.

  • AssetsPLCs, sensors, cameras, GPS
  • SystemsSAP, ERP, MES, SCADA, spreadsheets
  • PeopleOperators and managers: judgment and fixes

No credit card. Your data stays yours.